Midas® S2 Cartridge Hydrogen (H2) 90-1000 ppm P/N: MIDAS S2-E-H2X

SKU: MIDAS S2-E-H2X
Regular price £327.00 GBP

Have any questions? Contact our Sales Team who can help.

Sales@isscomplete.com

Midas® S2 Cartridge Hydrogen (H2) 90-1000 ppm P/N: MIDAS S2-E-H2X

Selectable gases Hydrogen (H2)
Cartridge Part Number MIDAS S2-E-H2X 2-year extended warranty
Sensor Technology Electrochemical sensor
Measuring Range H2 0 – 1000ppm
Default Alarm 1 H2 125ppm
Default Alarm 2 H2 250ppm
LDL, LAL H2 90ppm
Resolution H2 5ppm
Accuracy ≤ ± 5% of measured value
Response Time t62.5 Typical 30 seconds
Sensor Cartridge Life Expectancy
(Expiration Period)
24 months under typical application conditions
Extendable for 1 year through calibration after 
24 months
Operating Temperature
Effect of Temperature Sensitivity
0°C to +40°C (32°F to 104°F)
≤ ± 40% of measured value at 20°C
Operating Humidity 15 to 90% non-condensing
Operating Pressure 90 – 110kPa
Calibration Gas H2 500ppm
Warm Up Time < 10 minutes
Storage Temperature +5°C to +25°C (+41°F to +77°F)
ISS is not responsible for the data contained within this table.

Please download or contact us for further information: